Vertiv Expands 800 VDC Portfolio for AI Compute Pods and Data Halls

Key PointsVertiv lets operators choose where AC becomes DC instead of forcing one facility-wide…
View more
- Vertiv lets operators choose where AC becomes DC instead of forcing one facility-wide design.
- The PowerNexus solid-state transformer converts medium-voltage AC to 800 VDC in a single stage.
- Moving conversion outside the IT rack frees rack units for compute and isolates faults.
Vertiv on November 17, 2026 introduced the PowerDirect 9000 and PowerNexus MV SST, extending 800-volt direct-current (800 VDC) power beyond individual racks to AI compute pods and data halls. The PowerNexus is a 5 MW solid-state transformer that converts medium-voltage alternating current (AC) to 800 VDC in one stage.
The additions respond to rising AI power requirements by giving operators three places to set the AC-to-DC conversion boundary: beside an IT rack, ahead of a pod, or at the data hall’s medium-voltage connection. Vertiv expects AC and DC architectures to coexist, with no single adoption timetable. The accompanying architecture portfolio combines conversion, storage, distribution, protection, controls and monitoring, allowing 800 VDC to be introduced without committing an entire facility to one design.
Rack and Pod Conversion
The rack-level option remains the PowerDirect 5000, introduced in May 2026 for deployments that retain upstream AC infrastructure. It sits beside an IT rack and accepts 480 VAC, with 800 VDC or ±400 VDC output; Vertiv’s rating puts it at up to 800 kW, with battery backup designed for at least 50 seconds of hold-up. Moving conversion and storage outside the IT rack frees 8 to 16 rack units for compute, while using one power rack for one or two IT racks helps isolate faults and simplify maintenance.
Inside the compute rack, the 1U PowerDirect 3000 shelf converts 800 VDC to 54 VDC for compute trays. The 90 kW unit delivers up to 98.5% peak efficiency and 180% pulse power for 0.5 milliseconds in Vertiv’s specifications. The same shelf connects to the pod-level design, creating a common final conversion stage at the rack.
For a row or pod, the new PowerDirect 9000 consolidates conversion into one system ahead of the racks. The power center converts 480 VAC to 800 VDC, is rated by Vertiv at 1.5 MW and scales in 60 kW increments through 27 hot-pluggable power-supply units. PowerBar Track DC busway carries power overhead to the shelves, with a metered, breaker-protected drop at every rack.
EnergyCore Li5 battery cabinets connect directly to the DC bus. Each cabinet is rated by Vertiv at 200 kW of continuous backup and up to 98% conversion efficiency, with as many as six operating in parallel. Consolidating conversion, backup and distribution removes the need for a power rack beside every IT rack, recovers row space and supports mixed AC and DC loads, including colocation sites with different tenants, workloads and GPU generations.
Direct Medium-Voltage Conversion
At data-hall level, the PowerNexus’s outdoor, liquid-cooled container is rated by Vertiv at up to 98% AC-to-DC efficiency. It eliminates two to three intermediate conversion steps in conventional power trains, provides galvanic isolation between input and output, and can support a 4.8 MW super-pod reference architecture without chaining. Moving conversion outdoors can recover indoor space for compute, while fewer stages help reduce cumulative electrical losses.
When paired with external energy storage through a DC/DC converter on the 800 VDC bus, the system can ride through electrical faults and smooth AI workload fluctuations, according to Vertiv. Bidirectional power flow can improve grid power quality and provide active power support, while battery communication ports coordinate storage with rapid load changes. The containerized design also supports faster deployment and standardized replication across campuses.
DC Safety and Deployment Status
Safety features across the portfolio include touch-proof busbars, high-voltage isolation, midpoint grounding, ground-fault detection and arc-flash prevention. The accompanying service offerings are purpose-built for DC operating environments, rather than adapted from legacy AC procedures, according to Vertiv.
Vertiv is showcasing the portfolio at SC26 from November 17 to 22, 2026, with pilot programs, technical validation and customer-specific collaborative development underway. These options let operators match the conversion boundary to the facility: retain AC infrastructure during a rack retrofit, consolidate power around a pod, or move medium-voltage conversion outdoors for a campus. The choice extends beyond voltage, because each architecture also determines where backup, fault isolation and conversion losses are managed.